Ship's power is generated as 3-phase and is ungrounded. On a delta-wound transformer with 120 VAC line-to-line secondary, what is the voltmeter reading from line to ground:
A
Approx 67 volts for a normal balanced system with no faults
B
0 VAC for a system with that phase faulted to ground
C
120 VAC when another phase is faulted to ground
D
Any of the above